VERTICAL LAMINAR AIR FLOW ( VLAF ) CEILING SUSPENDED

Vertical Laminar Air Flow cabinets are designed for creation of a bacterial dust free air space.The work area is continuously supplied with positive pressure Hepa filtered vertical air flow & prevents contamination from operator and environment to work area. Air flow cabinets are used for work with low risk substances & material.

Category:

Description

 

Description – VERTICAL LAMINAR AIR FLOW ( VLAF )

MOC SS 304, 316,316L

HEPA Filter Imported Minipleat HEPA filter with hot melt technology, which conforms to EU-14 Grade at supply position with an efficiency rating better than 99.999% for 0.3 micron

Pre-filter
Pre-filters are made from Non-woven synthetic with HDPE mesh; conforms to EU-06 Grade, with an efficiency rating better than 95% down to 5 micron
Motor blower assembly
Motor blower designed of statically “and dynamically balanced for supply of sufficient capacity and static pressure to take care of air flow requirement for entire life of HEPA
Pressure Gauge  Magnehelic Gauge (0-25 mm: 1 Nos.) to monitor pressure drop across HEPA Filter
Lighting Fluorescent Light( 250 Lux) at work surface
ON/OFF Switches Keypad ON/OFF Switches for motor & lights
Switch socket 6/15 Amp single-phase switch socket use for external equipment
Control Panel Electrical Control Panel mounted in unit
Work table (SMVLAF) SS work table with due reinforcement
DOP Port
DOP test port at up stream of HEPA filter integrity test. (With PAO Solution)
Side Panel (SMVLAF) Toughened Glass /SS Sheet /Acrylic Sheet side panel screens for maximum visibility
Electrical Supply 230V AC 1-Ø 50 HZ/415V AC 3- Ø 50 HZ
Noise Level Less than 67 dB on Scale ‘A’ when Ambient is not greater than 55 dB on Scale ‘A’
Vibration Level Minimum
Air Flow Vertical

 

Optional Accessories
1) Anti-Static PVC strip Curtains
2) Suspension rod option available in MS and SS
3) U.V. Light with hour meter
4) SS 304. Cock for Gas and Air Foldable polycarbonate front hinged door
5) Audio Visual alarm indicating condition of HEPA filters
6) Clean down timer with operation hold Indicator
7) VFD based control systems
8) Photohelic guage / Digital pressure gauge to monitor of pressure drop across filter.
9) Sodium vapor lamp
10) Flame proof fitting

Reviews

There are no reviews yet.

Be the first to review “VERTICAL LAMINAR AIR FLOW ( VLAF ) CEILING SUSPENDED”

Your email address will not be published. Required fields are marked *